XL-808GBT22 Digital Electric Energy Meter Calibrator

The XL-808GBT22 digital energy meter calibrator features multiple calibration modes including actual load calibration, virtual calibration, and virtual load calibration. It complies with the new national standard "GB/T 17215.303 AC electrical measuring equipment Special requirements Part 3: Digital energy meters" and supports digital energy meter type testing according to the new version of the type evaluation outline "JJF XXXX-XXXX Digital Energy Meter Type Evaluation Outline."

Product Description

Product Introduction

The XL-808GBT22 digital energy meter calibrator features multiple calibration modes including actual load calibration, virtual calibration, and virtual load calibration. It complies with the new national standard "GB/T 17215.303 AC electrical measuring equipment Special requirements Part 3: Digital energy meters" and supports digital energy meter type testing according to the new version of the type evaluation outline "JJF XXXX-XXXX Digital Energy Meter Type Evaluation Outline."

Main Features
 

  • Complies with the new national standard "GB/T 17215.303 AC electrical measuring equipment Special requirements Part 3: Digital energy meters" and supports digital energy meter type testing according to the new version of the type evaluation outline "JJF XXXX-XXXX Digital Energy Meter Type Evaluation Outline."
  • Supports multiple calibration modes including actual load calibration, virtual calibration, and virtual load calibration.
  • Capable of simulating communication faults such as frame loss and channel abnormalities, comprehensively assessing the communication functions and fault tolerance of digital energy meters.
  • Compatible with IEC61850-9-1/-9-2/-9-2LE protocols, meets various fiber optic interface requirements, and has adaptive capabilities for communication parameters.
  • During actual load calibration, it can perform holographic analysis of IEC61850-9-1/IEC61850-9-2/IEC61850-9-2LE network messages, including network addresses, number of ASDUs, sampling rates, data waveforms, etc.
  • During virtual calibration and virtual load calibration, communication parameters such as the number of ASDUs and sampling points can be flexibly configured.
  • Users can freely edit automatic calibration schemes; our calibrator is shipped with multiple calibration schemes.
  • Supports multiple MU modes including single MU, single optical port dual MU, and dual optical port dual MU, enabling calibration of digital energy meters with different wiring modes.
  • Equipped with ST, SC fiber optic Ethernet interfaces and dual RJ45 electrical Ethernet interfaces to enhance communication reliability and facilitate connection to different interface metering devices.
  • Features automatic report generation and can customize calibration certificate templates according to customer requirements.
  • Supports digital standard source mode and digital standard meter mode when using digital traceability methods.
  • Retains analog traceability methods, supports traditional energy standards such as COM3003 (0.01 level), enabling accuracy calibration and value traceability.

 

Technical Specifications

1) Standard Digital Power Source
Rated Primary Voltage 6kV~1000kV
Rated Primary Current 100A~10000A
Virtual Secondary Voltage 57.7V/100V
Virtual Secondary Current 1A, 5A
Sampling Rate 4k (1 ASDU), 12.8k (8 ASDUs)
Voltage Output Accuracy <0.01% RD (>1kV)
Current Output Accuracy <0.01% RD (>10A)
Active Power Output Accuracy <0.02% RD (U>1kV, I>10A)
Fundamental Reactive Power Output Accuracy <0.02% RD (U>1kV, I>10A)
Frequency Output Range 45Hz–65Hz
Frequency Resolution 0.001Hz
Frequency Output Accuracy 0.001Hz
Active Energy Measurement Accuracy <0.02% RD (U>1kV, I>10A)
Fundamental Reactive Energy Measurement Accuracy <0.02% RD (U>1kV, I>10A)
2) Digital Measurement Indicators
Rated Primary Voltage 6kV~1000kV
Rated Primary Current 100A~10000A
Virtual Secondary Voltage 57.7V/100V
Virtual Secondary Current 1A, 5A
Sampling Rate 4k (1 ASDU), 12.8k (8 ASDUs)
Voltage Measurement Accuracy <0.01% RD (>1kV)
Current Measurement Accuracy <0.01% RD (>10A)
Active Power Measurement Accuracy <0.02% RD (U>1kV, I>10A)
Fundamental Reactive Power Measurement Accuracy <0.02% RD (U>1kV, I>10A)
Frequency Measurement Range 45Hz–65Hz
Frequency Measurement Resolution 0.001Hz
Frequency Measurement Accuracy 0.01Hz
Active Energy Measurement Accuracy 0.02% RD (U>1kV, I>10A)
Fundamental Reactive Energy Measurement Accuracy 0.02% RD (U>1kV, I>10A)
3) Analog Measurement Indicators
Voltage Measurement Range 0–120V
Voltage Measurement Accuracy (20–100V) 0.05% RD
Current Measurement Ranges 200mA, 1A, 5A, 10A
Current Accurate Measurement Range 50mA–10A 0.05% RD
Active Power Measurement Accuracy 0.05% RD PF=1 (50mA–10A)
0.1% RD PF=0.5L, 0.5C (50mA–10A)
Reactive Power Measurement Accuracy 0.2% RD PF≥0.5
Frequency Measurement Range 45Hz–65Hz
Frequency Measurement Resolution 0.001Hz
Frequency Measurement Accuracy 0.01Hz
Active Energy Measurement Accuracy 0.05% RD PF=1 (50mA–10A)
0.1% RD PF=0.5L, 0.5C (50mA–10A)
Reactive Power Measurement Accuracy 0.2% RD PF≥0.5
4) Energy Pulse Output of the Device
Output electric energy pulse (unit: imp/kWh or imp/kvarh) The settable range is 3600 to 2000000 imp/kWh or imp/kvarh output as optical isolation output, load capacity not greater than 5mA
5) Electric energy pulse input  
Input calibrated electric meter pulse (unit: imp/kWh or imp/kvarh) Decimal numbers can be input; verification cycle setting range: 1 to 100, maximum pulse frequency received is 100Hz
6) Other indicators
Operating power supply voltage range AC 220V±5% 50Hz
Power consumption About 30VA
Preheating time <15 minutes
Operating ambient temperature -10℃ to 55℃
Relative humidity ≤85%; corrosive gases
Dimensions 470mm×330mm×200mm
Overall weight 9kg

Product Document

File Name

Update Time

Related Products

XL-808S Portable Digital Energy Meter Calibrator


The XL-808S portable digital energy meter calibrator is mainly used for on-site calibration of digital energy meters that comply with the IEC61850 standard. It supports various calibration methods including virtual calibration and actual load calibration to suit different application scenarios.

XL-8016 Digital Electric Energy Meter Calibration Platform


The XL-8016 digital energy meter calibration platform can verify the basic errors of digital energy meters, voltage influence, frequency influence, harmonic influence, reverse phase sequence influence, voltage imbalance influence, sampling point influence, frame loss influence, standard deviation calibration, startup test, creeping test, and other verifications.

XL-8008 Digital Electric Energy Meter Calibration Platform


The series of digital electric energy meter calibration benches are designed in accordance with standards such as "GB/T 37006-2018 Digital Electric Energy Meter Inspection Device". They are used for laboratory batch verification of digital electric energy meters that comply with the IEC61850 standard, supporting virtual verification and virtual load verification methods.

0.01 Level Digital Electric Energy Meter Calibrator


Capable of outputting 8 channels of SMV messages, with the APPID, MAC address, number of channels, and channel numbers for each of the 8 SMV channels individually configurable;

XL-806 Digital Substation Integrated Calibrator


The XL-806 digital substation integrated calibrator can be widely used for on-site acceptance and subsequent maintenance inspection of photoelectric transformers and digital energy meters in digital substations. It can also be used for factory calibration of photoelectric transformers or digital energy meters.

XL-808 Digital Electric Energy Meter Calibrator


The XL-808 digital electric energy meter calibration instrument is designed in accordance with standards such as "GB/T 37006-2018 Digital Electric Energy Meter Inspection Device" and can perform laboratory or on-site calibration of digital electric energy meters.

Product Inquiry

Our staff will contact you within 24 hours (working days)