XL-809DCT DC Distribution Network Current Sensor Calibration System

The current sensor calibration system integrates traditional equipment (components) into one unit, built-in with a mutual inductor calibrator, standard current sensor, and programmable DC high current source. It features a high degree of automation and meets the current mutual inductor verification regulations.

Product Description

 

Main Functions

  • Realize error verification of DC current sensors.
  • The current sensor verification system integrates traditional equipment (components), built-in mutual inductor calibrator, standard current sensor, and programmable DC high current source, with a high degree of automation, meeting the current mutual inductor verification regulations.
  • All devices (components) within the device can be individually sent for inspection according to existing verification regulations.
  • Equipped with primary current verification point monitoring instruments, capable of displaying primary current verification points.
  • Large screen display with built-in touch screen, full Chinese operation prompts, easy operation, real-time display of measurement data, and statistical analysis.
  • Can display the waveform of the sensor under verification in real time to monitor waveform distortion of the sensor being tested.
  • Verification schemes can be freely edited as needed to achieve fully automatic verification.
  • Reports can be generated based on customer-provided templates, which can be freely edited.
  • This product has strong adaptability and scalability, supporting future upgrades.

 

Technical Specifications

 

 

1. Calibrator Technical Specifications

Accuracy Level

Level 0.05

Standard Current Input Range

DC 0-0.4A

Standard Measurement Range

1%-100% In

Small Signal Input Range Under Test

0–10V

Measurement Range Under Test

1%-120% Un

Standard Current Ranges

0.0032A, 0.016A, 0.08A, 0.4A

Small Signal Input Ranges Under Test

0.15V, 0.5V, 2V, 10V

Load Resistance Ranges

20kΩ, 50kΩ, 100kΩ, 200kΩ, 500kΩ, 1MΩ, 2MΩ

Load Accuracy

3%

2. Programmable DC High Current Source Specifications

Output Range

DC 0-600A

Accuracy

1%RD

Ripple Factor

Better than 0.5% FS + 10mVrms

Capacity

3kW

3. Standard Current Transformer Specifications

Input Range

DC 0-600A

Standard Current Transformer Ratio

600A: 0.4A

Accuracy Level

Level 0.02

4. Other Specifications

Industrial Control Computer Parameters

19 inches

Processor: I5

4G Memory

Operating Power Supply

AC 220V±5% 50Hz

Maximum Total Power Consumption

≈3500VA

Warm-up Time

<15 minutes

Weight

Approximately 75kg

Operating Temperature

-5℃ to +40℃

Relative Humidity

≤80% (no condensation or corrosive gases)

Product Document

File Name

Update Time

Related Products

XL-809DPT DC Distribution Network Voltage Sensor Calibration System


XL-809DPT DC distribution network voltage sensor calibration system, equipped with a transformer calibrator, 10kV fully shielded DC standard divider, and programmable adjustable DC high voltage source. It features a high degree of automation and meets the current sensor verification regulations.

Product Inquiry

Our staff will contact you within 24 hours (working days)