XL-809DPT DC Distribution Network Voltage Sensor Calibration System
XL-809DPT DC distribution network voltage sensor calibration system, equipped with a transformer calibrator, 10kV fully shielded DC standard divider, and programmable adjustable DC high voltage source. It features a high degree of automation and meets the current sensor verification regulations.
Product Description
Main Functions
- Implements ratio difference calibration for DC distribution network voltage sensors.
- The DC voltage sensor calibration system integrates traditional equipment (components) and is equipped with a transformer calibrator, 10kV fully shielded DC standard voltage divider, and programmable adjustable DC high voltage source. It has a high degree of automation and meets current sensor verification regulations.
- All equipment (components) within the device can be individually sent for inspection according to existing verification regulations.
- Equipped with primary voltage monitoring instruments that can display primary voltage.
- Large screen display with built-in touch screen, full Chinese operation prompts, easy operation, real-time display of measurement data, and statistical analysis.
- Can display the waveform of the sensor being calibrated in real time to monitor waveform distortion of the sensor under test.
- Calibration schemes can be freely edited as needed to achieve fully automatic calibration.
- Can generate and print test reports based on customer-provided templates, which can be freely edited.
- This product has strong adaptability and scalability, supporting future upgrades.
Technical Specifications
1. Transformer Calibrator Specifications | |
Accuracy Class | Class 0.05 |
Standard and Tested Input Range | 0~10V |
Standard and Tested Input Ranges | 0.15V, 0.5V, 2V, 10V |
Measurement Range | 1%-120% Un |
Input Impedance | ≥100MΩ |
Load Resistance Ranges | 20kΩ, 50kΩ, 100kΩ, 200kΩ, 500kΩ, 1MΩ, 2MΩ |
Load Accuracy | 3% |
2. Programmable Adjustable DC High Voltage Source | |
Output Range | 0-10kV |
Accuracy | 1%RD |
Stability | Better than 0.1% (after thermal stabilization) |
Ripple Factor | Better than 0.1% RMS |
3. 10kV Fully Shielded DC Standard Voltage Divider | |
Input Range | 0-10kV |
Standard Voltage Transformer Specifications | 10kV: 10V |
Standard Voltage Transformer Accuracy | Class 0.02 |
4. Other Specifications | |
Industrial Computer Parameters | Display: 19 inches |
Processor: I5 | |
4GB Memory | |
Power Supply | AC220V±5%, 50Hz |
Total Power Consumption | < 1000VA |
Warm-up Time | <15 minutes |
Weight | Approximately 65kg |
Operating Temperature | -5℃ to +40℃ |
Relative Humidity | ≤80% (no condensation or corrosive gases) |
Product Document
File Name
Update Time
Related Products
XL-809DCT DC Distribution Network Current Sensor Calibration System
The current sensor calibration system integrates traditional equipment (components) into one unit, built-in with a mutual inductor calibrator, standard current sensor, and programmable DC high current source. It features a high degree of automation and meets the current mutual inductor verification regulations.