XL-3602 DC Current Transformer Tester
The XL-3602 DC-resistant transformer calibrator is mainly used for DBI DC bias-resistant low-voltage current transformer calibration. It features power frequency error testing, power frequency superimposed DC component testing, sine half-wave testing, and harmonic testing functions.
Product Description
Product Introduction
XL-3602 Anti-DC Transformer Tester Mainly used for DBI anti-DC bias low-voltage current transformer testing, featuring power frequency error test, power frequency superimposed DC component test, sine half-wave test, and harmonic test functions.
Main Uses
- Capable of verifying the angular and ratio errors of low-voltage current transformers under DC, harmonic, and power frequency current signals for various frequency signals and full-wave signals;
- Tested signals compatible with rated secondary values of 1A and 5A;
- Standard signals compatible with resistive voltage division output and DC current input.
Main Technical Features
- Uses 24Bit AD chip and 512 times oversampling technology, greatly expanding bandwidth and improving accuracy.
- Employs multi-range automatic switching and FIR filters to enhance dynamic range and signal-to-noise ratio.
- Can display waveform, frequency, amplitude, phase, and other data for comprehensive analysis of transformer performance.
- Equipped with an industrial control computer, 800*600 resolution with touch screen for easy operation.
- Comes with powerful and easy-to-use software, operable on industrial control computers or laptops.
- Can statistically analyze mean, variation, extreme values, and multiple errors of ratio and phase differences, enabling comprehensive verification of electronic transformer stability and linearity.
- Supports multiple harmonic analyses and verification of harmonic accuracy for electronic transformers.
Technical Specifications
Fundamental Measurement Accuracy | ||||
Current Measurement Accuracy | 5%~120%In, 0.02%RD (In=1A or In=5A) | |||
(AC, DC, AC+DC) | 1%~5%In, 0.05%RD (In=1A or In=5A) | |||
Standard Input Range | 0%~120%In (In=1A or In=5A) | |||
Tested Input Range | 0%~120%In (In=1A or In=5A) | |||
Accuracy Class | 0.02 Class | |||
Ratio Error Measurement Accuracy | 0.02% | |||
Phase Error Measurement Accuracy | 0.6′ | |||
1A Standard Input Terminal Impedance | Not greater than 0.07Ω | |||
5A Standard Input Terminal Impedance | Not greater than 0.01Ω | |||
1A Tested Input Terminal Impedance | Not greater than 0.07Ω | |||
5A Tested Input Terminal Impedance | Not greater than 0.01Ω | |||
Measurement Frequency Range | 20~440Hz | |||
DC Measurement Accuracy | ||||
DC Current Measurement Accuracy | 0.1 Class | |||
Harmonic Measurement Accuracy | ||||
Harmonic Orders | 2~4th | 5~6th | 7~9th | 10~25th |
Harmonic Ratio Error Measurement Accuracy (%) | 0.1 | 0.2 | 0.5 | 1 |
Harmonic Phase Difference Measurement Accuracy (°) | 0.2 | 0.5 | 1 | 2 |
Other Parameters | ||||
Power Supply | AC 220V±10% 50 Hz 150VA |