XL-3642 Low Frequency Current Transformer Calibrator
The XL-3642 low-frequency current transformer calibrator can test electromagnetic (low-frequency) current transformers with a rated frequency of 15Hz~65Hz (such as 20Hz) that comply with "GB/T 20840.2 Instrument Transformers Part 2: Supplementary Technical Requirements for Current Transformers" and "GB/T 20840.8 Instrument Transformers Part 8: Electronic Current Transformers."
Product Description
Product Introduction
XL-3642 Low Frequency Current Transformer Calibrator It can test electromagnetic (low frequency) current transformers with rated frequencies from 15Hz to 65Hz (such as 20Hz) that comply with "GB/T 20840.2 Transformers Part 2: Supplementary Technical Requirements for Current Transformers" and "GB/T 20840.8 Transformers Part 8: Electronic Current Transformers." Based on the digital comparison transformer calibration principle, the core uses a dual-CPU architecture, offering powerful functions. With a 24-bit AD chip and 512 times oversampling technology, the bandwidth is greatly expanded and measurement accuracy is improved. At the same time, an FIR filter is used to enhance dynamic range and signal-to-noise ratio. The independently developed human-machine interaction software adopts a popular design, making it simple and convenient to use.
Main Functions
- Error (ratio error, phase error) test of low-frequency voltage/current transformers at 15Hz~30Hz frequency;
- Power frequency error (ratio error, phase error) test of voltage/current transformers;
- 2nd to 40th harmonic error (ratio error, phase error) test of voltage/current transformers;
- Influence test of 2nd to 40th harmonic error (ratio error, phase error) of voltage/current transformers;
- DC voltage/current transformer error test;
- Harmonic content analysis and waveform distortion rate calculation of the secondary output of voltage/current transformers, and testing of ratio error and phase error for each harmonic order;
Technical Specifications
1. Accuracy Class | |
0.05 Class ( Ratio Error < 0.05% , Phase Error < 2' | |
2. Measurement Accuracy | |
Fundamental Measurement Accuracy | |
Current Measurement Accuracy | 50mA~6A : 0.05%RD ; |
10mA~50mA : 0.1%RD ; | |
Voltage Measurement Accuracy | 10V~120V , 0.05%RD |
Input Range | 0~120V 、 0~6A |
Ratio Error Measurement Accuracy | 0.05% |
Phase Error Measurement Accuracy | 2 ' |
DC Measurement Accuracy | 0.10% |
Current Input Terminal Impedance | Not greater than 0.1Ω (AC mode), not greater than 5Ω (DC mode) |
Measurement Frequency Range | 15~50Hz |
3. Human-Machine Interface | |
Display | TFT LCD Resolution 800*600 |
Operation | Touch screen operation, industrial computer has USB port, can connect USB mouse and keyboard |
Dimensions | 470mm×330mm×200mm |
Total Weight | 10kg |
5) Environmental Conditions | |
Power Supply Voltage | AC 220V ± 10% 50 Hz |
Ambient Air Temperature | (-10 ℃ ~ 55 ℃ ) |
Maximum Relative Humidity | <85% |
Product Document