XL-3605 Wide Range Current Transformer Calibrator
The XL-3605 wide-range current transformer calibrator is mainly used for calibrating the phase angle difference and ratio difference of current transformers under signals including power frequency current, harmonics, and other frequency signals as well as full-wave signals. Calibration items include ratio difference, phase angle difference, harmonic analysis, and harmonic accuracy verification.
Product Description
Product Introduction
XL-3605 Wide Range Current Transformer Calibrator Mainly used for calibrating the angle difference and ratio difference of current transformer signals at various frequencies and full-wave signals under power frequency current, harmonics, and other signals. Calibration items include: ratio difference, angle difference, harmonic analysis, harmonic accuracy verification, etc.
Main Features
- Uses 24Bit AD chip and 512 times oversampling technology to greatly expand bandwidth and improve accuracy.
- Adopts multi-gear automatic switching and FIR filter to improve dynamic range and signal-to-noise ratio.
- Can display waveform, frequency, amplitude, phase and other data for comprehensive analysis of transformer performance.
- Equipped with an industrial control computer, resolution 800*600 with touch screen for easy operation.
- Comes with powerful and easy-to-use software that can run on industrial control computers or laptops.
- Can statistically analyze the mean, variation, extreme values, and multiple errors of ratio difference and angle difference, enabling comprehensive verification of current transformer stability and linearity.
- Features full-range multi-gear automatic shifting, wide range current transformer from 0.1% to 200% In full range, achieving better low calibration point performance.
- Can perform multiple harmonic analyses and verify the accuracy of each harmonic of the current transformer.
Technical Specifications
1. Accuracy Class | ||||
Class 0.05 (Ratio difference < 0.05%, Angle difference < 2') | ||||
2. Wide Range Transformer Calibrator Specifications | ||||
Current Measurement Accuracy | 0.1%~200% In, 0.02% RD (In=5A) | |||
Standard Input Range |
0.1%~200% In (In=5A) Ranges: 0.1mA 0.5mA 2.5mA 10mA 50mA 0.2A 1A 10A |
|||
Tested Input Range (Current Type) |
0.1%~200% In (In=5A) Ranges: 0.1mA 0.5mA 2.5mA 10mA 50mA 0.2A 1A 10A |
|||
Ratio Error Measurement Accuracy | 0.02% | |||
Phase Error Measurement Accuracy | 0.6 minutes | |||
5A Standard Input Terminal Impedance | Not greater than 0.1Ω | |||
5A Tested Input Terminal Impedance | Not greater than 0.1Ω | |||
Measurement Frequency Range | 40~65Hz | |||
3. Human-Machine Interface |
||||
Display |
TFT LCD resolution 800*600 |
|||
Operation |
Touch screen operation, industrial control computer has USB ports, can connect USB mouse and keyboard |
|||
Dimensions |
470mm×330mm×200mm |
|||
Total Weight |
10kg |
|||
4. Environmental Conditions |
||||
Power Supply Voltage |
AC 220V±10% 50 Hz |
|||
Ambient Air Temperature |
(-10℃ ~ 55℃) |
|||
Maximum Relative Humidity |
<85% |