XL-828 Digital Electric Energy Meter Calibration Instrument Overall Verification Device

The XL-828 digital electric energy meter calibration instrument integrated verification device can be used for energy error verification and effective value verification of digital electric energy meter calibration instruments. It is also an integrated digital meter source device that combines a digital standard meter, digital standard source, and analog standard source.

Product Description

Product Introduction                          

XL-828 Digital Energy Meter Calibration Instrument Integrated Verification Device It can be used for energy error verification and effective value verification of digital energy meter calibration instruments. It is also an integrated digital meter source device combining digital standard meter, digital standard source, and analog standard source.
 

Functional Features                         

  • Compatible with IEC6 1850-9-1 IEC6 1850-9-2 IEC6 1850-9-2 LE protocol, with adaptive capability for communication parameters.
  • In digital standard source mode, it can flexibly configure sampling points, number of ASDUs, SVID, APPID, and other communication parameters.
  • Supports fully automatic verification in digital standard source mode and analog-digital verification mode. The calibration instrument can automatically complete verification and save data according to your configured verification plan, which can be freely edited using the plan editing system.
  • Integrates a high stability three-phase standard power source, uses high-precision A/D for internal sampling, featuring simple wiring and high accuracy.
  • Equipped with multiple Ethernet communication interfaces (ST fiber optic port, SC fiber optic port, RJ45 network port) to improve compatibility with the device under test.

 

Technical Specifications                         

 

1) Internal A/D Sampling Module Accuracy
Voltage Measurement Accuracy 0.02% RD
Current Measurement Accuracy 0.02% RD
Active Power Measurement Accuracy 0.02% RD PF=1
0.05% RD PF=0.5
Reactive Power Measurement Accuracy 0.05% RD PF≥0.5
Frequency Measurement Frequency Measurement Range: 40Hz~60Hz
Frequency Resolution: 0.0001Hz
Frequency Accuracy: 0.001Hz
2) Built-in Power Source Output Accuracy
Output 0.02% RD
Current Measurement Accuracy 0.02% RD
Active Power Output Accuracy 0.02% RD PF=1
0.05% RD PF=0.5
Reactive Power Output Accuracy 0.05% RD PF≥0.5
Frequency Output Frequency Measurement Range: 40Hz~60Hz
Frequency Resolution: 0.002Hz
Frequency Accuracy: 0.004Hz
3) Virtual Digital Source Accuracy
Voltage Output Accuracy 0.01% RD
Current Output Accuracy 0.01% RD
Active Power Output Accuracy 0.01% RD PF=1
0.02% RD PF=0.5L or 0.5C
Reactive Power Output Accuracy 0.02% RD PF≥0.5
Frequency Output Frequency Output Range: 40Hz~60Hz
Frequency Output Resolution: 0.0001Hz
Frequency Output Accuracy: 0.001Hz
4) Digital Standard Meter Accuracy
Voltage Measurement Accuracy 0.01% RD
Current Measurement Accuracy 0.01% RD
Active Power Measurement Accuracy 0.01% RD PF=1
0.02% RD PF=0.5L or 0.5C
Reactive Power Measurement Accuracy 0.02% RD PF≥0
Active Energy Measurement Accuracy 0.01% RD PF=1
0.02% RD PF=0.5L or 0.5C
Reactive Energy Measurement Accuracy 0.02% RD PF≥0.5
Frequency Measurement Frequency Measurement Range: 40Hz~60Hz
Frequency Measurement Resolution: 0.0002Hz
Frequency Measurement Accuracy: 0.001Hz
5) Energy Pulse Output
Energy Output Pulse Constant Constant supports floating point values, imp/kW.h or imp/kvar.h
Load Capacity Not greater than 5mA, output is optically isolated
6) Energy Pulse Input
Pulse Constant of Device Under Test Constant supports floating point values, imp/kW.h or imp/kvar.h
Verification Cycle Setting Range 1~100
Maximum Pulse Frequency Reception 100Hz
7) Other Specifications
Operating Power Supply Voltage Range AC 220V±5% 50Hz
Power Consumption <300VA
Warm-up Time <15 minutes
Operating Temperature -10℃~55℃
Relative Humidity ≤85%; No corrosive gases
Dimensions 570mm×480mm×190mm
Overall Weight 24kg

Product Document

File Name

Update Time

Related Products

XL-847C DC Current Transformer Calibration Instrument Overall Verification Device


XL-847C DC Transformer Tester Overall Calibration Device, used for error calibration of DC transformer testers with analog input based on FT3 input.

XL-847 Electronic Transformer Calibrator Overall Verification Device


The series of integrated calibration devices for electronic transformer calibrators can perform comprehensive calibration of electronic transformer calibrators. They are used by provincial-level and above electric power research institutes, metrology research institutes, and other units for comprehensive testing of electronic transformer calibrators below 0.05 grade.

XL-882-001 Digital Electric Energy Transmission Detection Unit


XL-882-001 Digital Electric Energy Transmission Detection Unit, capable of testing 0.05 level digital electric energy meters for calibration. Composed of multiple modules, each module is independently traceable.

XL-892-001 Electronic Transformer and Merging Unit Calibration Instrument Measurement and Transmission Detection Unit


The XL-892 digital metrology laboratory testing platform can be used by provincial-level and above power research institutes, metrology science research institutes, and other units for comprehensive testing of electronic transformer calibrators and merging unit testers below 0.05 grade.

Product Inquiry

Our staff will contact you within 24 hours (working days)