XL-809 Electronic Transformer Calibrator
The XL-809 electronic transformer tester (small signal input) is suitable for laboratory and on-site precision calibration of electronic transformers with small signal output that comply with IEC60044-7/8 standards. It has an accuracy level of 0.05 and can perform calibration of electronic transformers with small signal output types of 0.2S level and below.
Product Description
Product Introduction
XL-809 Electronic Transformer Tester (Small Signal Input ) The core adopts a dual-CPU architecture, with powerful functions, greatly expanding bandwidth with a 24Bit AD chip and 512 times oversampling technology, improving measurement accuracy. At the same time, multi-gear automatic switching and FIR filters are used to improve dynamic range and signal-to-noise ratio. Developed with LabView management software, the interface is beautiful and easy to use. The power supply and sampling input adopt a large number of electromagnetic compatibility measures, capable of adapting to complex field test environments. The portable design scheme is convenient for laboratory and field testing. Suitable for laboratory and field precision calibration of electronic transformers with small signal output that meet IEC60044-7/8 standards, with an accuracy of 0.05 level, capable of calibrating electronic transformers with small signal output types of 0.2S and below.
Main Functions
- The XL-809 tests AC sensors that comply with the "T/ZDG018-2018 Technical Conditions for 10kV and 20kV Distribution Network AC Sensors."
- Realizes the calibration of ratio error and phase error of electronic transformers;
- Displays relevant information such as voltage, current, and frequency of the current primary conductor, facilitating comprehensive evaluation of the calibrated parameters;
- Test reference standards: "T/ZDG018-2018 Technical Conditions for 10kV and 20kV Distribution Network AC Sensors," "JJG313-2010 Current Transformer for Measurement," "JJG314-2010 Voltage Transformer for Measurement";
- Can display the waveform of the calibrated sensor in real time to monitor waveform distortion of the tested transformer;
- Convenient error recording at calibration points; clicking report generation saves the recorded error data for easy archiving or error analysis;
- Large screen display with built-in touch screen, full Chinese operation prompts, easy operation, real-time display of measurement data, and statistics. This product has strong adaptability and scalability, supporting future upgrades.
Technical Specifications
Tester Technical Specifications | |
Tester Accuracy Level | Level 0.05 (ratio error better than 0.05%, phase error better than 2′) |
Standard Voltage Input Range | 0~120V |
Standard Voltage Measurement Range | 20V~120V 0.05%RD 1V~20V 0.1%RD |
Standard Current Input Range | 0~6A |
Standard Current Input Gears | 50mA, 100mA, 1A, 5A |
Standard Current Measurement Range | 10mA~6A 0.05%RD |
Tested Small Signal Input Range | 0~8.5V (some older equipment 0~7V) |
Tested Small Signal Input Impedance | 200MΩ |
AC Analog Small Signal Output | |
Output Range | 0~7V |
Output Accuracy | 0.05%RD (200mV~7V) |
Other Specifications | |
Power Supply | AC 220V±5% 50Hz |
Total Power Consumption | About 30VA |
Operating Temperature | -10℃~50℃ |
Relative Humidity | ≤85% No corrosive gases |
Dimensions | Length 449mm × Width 271mm × Height 182mm |
Total Weight | 8.9kg |
Product Document
File Name
Update Time
Related Products
XL-809RED Three-Phase Digital Comparative Transformer Calibrator
XL-809E Digital Comparison Transformer Calibrator
XL-807H Power Frequency Harmonic Current Transformer Calibrator
XL-809RM Three-Phase AC Sensor Calibrator
XL-809RE Three-Phase AC Sensor Calibrator
XL-8093I Network Configuration AC Sensor Calibrator
XL-8093U Network Configuration AC Sensor Calibrator
XL-809R Network Configuration AC Sensor Calibrator
XL-3270 Programmable Wideband Current Source
Product Inquiry